The ACCO-KP2 module is designed to control a single door within the ACCO or ACCO NET access control system. The module can also be used as a standalone device. Available methods of user authorization include: user code, proximity card (passive transponder such as a card, tag, or other), or DALLAS iButton
The device is characterized by wide configuration options, e.g. in terms of user rights and time schedules for each of them. Over 24,000 events can be registered in the non-volatile module's memory. ACCO-KP2 is provided with 2 OC-type outputs (e.g. to operate two-way and revolving gates, tripods) and 1 relay output for operating an electromagnetic lock or another door activating device. The inputs and outputs of the module can also be used for its cooperation, e.g. with an alarm system.
Programming the ACCO-KP2 and the functions performed by this device differ depending on the system of which the controller is a part. When working in the ACCO system, configuration takes place in the ACCO-SOFT-LT program, and the computer on which it is installed is connected to the controller using the ACCO-USB converter via the RS-485 bus. In the case of the ACCO NET system, the controller connects to the ACCO-NT access control panel via the RS-485 bus. In turn, communication between the control panel, the system server and the computer with the ACCO Soft configuration program is provided with the use of the TCP/IP protocol.
support for single door with entry and exit authorization
standalone or ACCO / ACCO NET system operation mode
1,024 users (standalone or ACCO system operation mode)
user rights definition
possibility to assign the user a code, proximity card (passive transponder in the form of a card, tag, etc.) or DALLAS iButton
support for various terminals enabling the user identification - keypads and proximity card readers
support for terminals using various transmission protocols
EM Marin (SATEL terminals)
Wiegand 26, 32, 34, 36, 40, 42, 56
DALLAS
time schedules
256 weekly schedules
256 daily schedules
256 time frames
holiday access schedules
non-volatile 24,576 event log
registering information on time attendance control
protection against multiple use of the same code / card for access (anti-passback)
programming means:
standalone or ACCO system operation mode - computer with the ACCO-SOFT-LT program
ACCO NET operation mode - computer with the ACCO Soft program
non-volatile FLASH settings memory
firmware update without the necessity to dismantle the module
locally (single module) – via USB port of the module
via RS-485 bus (single or many modules) – using the ACCO-USB converter
remotely in broadcast mode (single or many controllers) - via the ACCO-NT control panel (ACCO NET system operation mode)
scheduled door locking and unlocking
programmable limits on number of accesses (only ACCO system operation mode)
power status control in cooperation with the APS-412 / APS-612 / APS-1412 power supply - connected to the APS connector in the module
Note
The ACCO-KP2 module has been supported as part of the ACCO NET version 1.8 or newer.
ما آماده پاسخگويي در تمام زمينه هاي مربوط به فعاليت های گروه فنی مهندسی پارس ایمن لاریچه هستيم. لطفا جهت ارتباط با ما، درخواست خود را از طریق ایمیل برای ما ارسال فرمایید و یا از طریق تلفن با ما ارتباط برقرار کنید.